Outside Sensors FW-T1G
• Passive sensors for acquiring the outside temperature and – to a lesser
degree – solar radiation, the wind effect and the temperature of the wall.
• Range of use -40/50…+70 °C / 5…95 % r. F.
Use
The QAC… outside sensors are for use in heating, ventilation and air conditioning
plants as:
• Reference sensors for weather-compensated control
• Measuring sensors, e.g. for optimization, measured value indication, or for connec-
tion to a building automation and control system
Type summary
Type reference Sensing element Range of use Time constant
QAC22 LG-Ni 1000 − 50...+ 70 °C ca. 14 min
QAC32 NTC 575 − 50...+ 70 °C ca. 12 min
(linearized)
QAC2010 Pt 100 − 50...+ 70 °C ca. 14 min
QAC2012 Pt 1000 − 50...+ 70 °C ca. 14 min
QAC2030 NTC10k − 40...+ 70 °C ca. 14 min
FW-T1G T1 (PTC) − 50...+ 70 °C ca. 14 min
Ordering and delivery
When ordering, please give name and type reference, e.g.:
Outside sensor QAC22.
CE1N1811E
Building Technologies
20.11.2006 HVAC Products
Equipment combinations
The outside sensors are suited for use with all types of controllers capable of acquiring
and handling the sensor’s measured value.
Function
The outside sensor acquires the outside temperature and − to a lesser degree − solar
radiation, the wind effect and the temperature of the wall. The sensing element
changes its resistance value as a function of the temperature.
Sensing elements Characteristic: Accuracy:
R [Ω]
LG-Ni 1000
∆ϑ [K]
1811D01
1400 2.0
1811D02
1200 1.0
1000 0.0
800 −1.0
600 ϑ −2.0 ϑ
−50 −40 −30 −20 −10 0 10 20 30 40 50 60 70 80 [°C] −50 −40 −30 −20 −10 0 10 20 30 40 50 60 70 80 [°C]
R [Ω] ∆ϑ [K]
NTC 575
700
1811D03
3.0
1811D04
650 2.0
1.0
600
0.0
550
−1.0
500
−2.0
450 ϑ −3.0 ϑ
−50 −40 −30 −20 −10 0 10 20 30 40 50 60 70 80 [°C] −50 −40 −30 −20 −10 0 10 20 30 40 50 60 70 80 [°C]
R [Ω]
Pt 100 (class B)
∆ϑ [K]
1811D05
140
0.8 1811D06
120
0.4
100 0.0
−0.4
80
−0.8
60 ϑ ϑ
−50 −40 −30 −20 −10 0 10 20 30 40 50 60 70 80 [°C] −50 −40 −30 −20 −10 0 10 20 30 40 50 60 70 80 [°C]
R [Ω]
Pt 1000 (class B)
∆ϑ [K]
1811D07
1400
1811D06
0.8
1200
0.4
1000 0.0
−0.4
800
−0.8
600 ϑ ϑ
−50 −40 −30 −20 −10 0 10 20 30 40 50 60 70 80 [°C] −50 −40 −30 −20 −10 0 10 20 30 40 50 60 70 80 [°C]
2/4
Building Technologies Outside sensors QAC... CE1N1811E
HVAC Products 20.11.2006
R [Ω]
NTC 10k ∆ϑ [K]
1000000
1811D09
1.20
1811D08
1.00
0.80
0.60
100000
0.40
0.20
0.00
-0.20
10000 -0.40
-0.60
-0.80
-1.00
1000 ϑ -1.20 ϑ
-40 -30 -20 -10 0 10 20 30 40 50 60 70 80 [°C] -40 -30 -20 -10 0 10 20 30 40 50 60 70 80 [°C]
R [Ω]
T1 (PTC)
3200 ∆ϑ [K]
1819D01
3000 5.0
1819D02
2800 4.0
3.0
2600
2.0
2400 1.0
2200 0.0
2000 −1.0
−2.0
1800
−3.0
1600 −4.0
1400 ϑ −5.0 ϑ
−40 −30 −20 −10 0 10 20 30 40 50 60 70 80 [°C] −40 −30 −20 −10 0 10 20 30 40 50 60 70 80 [°C]
Legend R Resistance in Ohm
ϑ Temperature in degrees Celsius
∆ϑ Temperature differential in Kelvin
Mechanical design
The sensor has a plastic housing with a removable cover.
The connection terminals can be accessed after removal of the cover.
Cable entry is either from the rear (concealed wiring) or from below (surface-run wires).
A cable entry gland can be screwed into the bottom of the housing.
Engineering notes
The permissible cable lengths depend on the type of controller with which the sensor is
used. They are specified in the Data Sheet of the relevant controller.
Mounting notes
Depending on use, the outside sensor must be located as follows:
Mounting location • For control:
On the wall of the house or building that has the windows of the occupied rooms, but
the sensor must not be exposed to the morning sun. In case of doubt, it should be
mounted on the wall facing north or north-west
• For optimization:
Always on the coldest wall of the house or building (normally the wall facing north).
The sensor must never be exposed to the morning sun
Mounting height Preferably in the middle of the house or building or heating zone, but at least 2.5 m
above the ground.
The sensor must not be fitted at the following locations:
• Above windows, doors, air extracts or other heat sources
• Below balconies or the eave of the roof
To prevent measuring errors due to air circulation, the cable conduit at the sensor
should be sealed.
The sensor may not be painted over.
Mounting Instructions are printed on the packaging.
3/4
Building Technologies Outside sensors QAC... CE1N1811E
HVAC Products 20.11.2006
Technical data
Functional data Range of use refer to "Type summary"
Sensing element refer to "Type summary"
Time constant refer to "Type summary"
Accuracy refer to "Function"
Type of measurement and output passive
Protective data Degree of protection of housing IP 54 to IEC 529
Safety class III to EN 60 730
2 2
Electrical connections Screw terminals for 2 x 1.5 mm or 1 x 2.5 mm
Cable entry for cable gland (e.g. M 16 x 1.5)
Perm. cable length refer to "Engineering notes"
Environmental conditions Operation
Climatic conditions .
Temperature − 40...+ 70 °C .
Humidity 0 . . . 1 0 0 % r. h.
Storage / transport to IEC 721-3-2
Climatic conditions class 2K3
Temperature − 25...+ 65 °C
Humidity < 95 % r. h.
Mechanical conditions class 2M2
Materials and colors Base plastic (ASA)
Cover plastic (ASA), RAL9003
Packaging cardboard
Weight Incl. packaging approx. 0.093 kg
Internal diagram
1811G01
B M
The internal diagram is identical for all types of outside sensors covered by this Data
Sheet.
The connecting wires are interchangeable.
Dimensions
5,5 3
92
5,5
20,7
4
6
.
80 50 Ø 16
.
25 24,5
1811M03
49,5
Drilling plan
Dimension in mm
4/4 ©2004 - 2006Siemens Switzerland Ltd Subject to alteration
Building Technologies Outside sensors QAC... CE1N1811E
HVAC Products 20.11.2006